A #1 copper conductor will limit the voltage drop to 3% or less when supplying 95 amps for 200 feet on a 208 volt system. This size will allow the conductor to be loaded to 76 amps. 95 x 80% = 76 amps
Conductors are only allowed to be loaded to 80% or their rated capacity. If you need the full 95 amps then you would need to use a wire with a rating of 120 amps. 120 x 80% = 96 amps.
A 1/0 copper conductor will limit the voltage drop to 3% or less when supplying 120 amps for 200 feet on a 208 volt system.