Why does an alternators voltage rise when it is loaded down with a leading load?

1 answer

Answer

1199451

2026-03-14 13:45

+ Follow

Because in the leading load or capacitive load the armature reaction is magnetizing.Here the stator flux adds up rotor flux and so the net flux of alternator increases and the net flux produces alternator's voltage.Hence the alternator's voltage rises.

ReportLike(0ShareFavorite