Is it acceptable or required for bathroom lights to be connected to the GFCI outlet such that if the GFCI trips the lights go out?

1 answer

Answer

1095113

2026-03-28 13:35

+ Follow

It is acceptable for the lights to be wired this way but not required. The GFCI is only required to protect the actual receptacle(s) in the bathroom. ----

If you do not understand the work well enough to accomplish it yourself properly and safely, don't try it. Consult a professional electrician, as they are proficient enough to do it properly and safely. When working on electrical circuits and equipment, make sure to de-energize the circuit you will be working on. Then test the circuit with a definitive means to make sure it is off (multimeter with metal tipped leads, voltage tester with metal tipped leads, etc., not a non-contact tester, which is non-definitive.)