There is no single conductor that will handle 1500 amps. For ease of handling, the conductors should be installed in parallel, triple or quad runs.
For a parallel run, 2 - 2000 MCM with an insulation factor of 90 degrees C will give you a total ampacity of 1550 amps.
For a triple run, 3 - 750 MCM with an insulation factor of 90 degrees C will give you a total ampacity of 1500 amps.
For a quad run, 4 - 500 with an insulation factor of 90 degrees C will give you a total ampacity of 1580 amps.