How many ground rods are required for a 200amp service in Indianapolis?

1 answer

Answer

1230317

2026-03-01 01:10

+ Follow

According to the NEC, if the ground rod supplements another grounding electrode such as a metal water pipe, you are required 1. If the ground rod or rods is your only grounding electrode, you are required at least 2, at least 6 feet apart. Check with your local jurisdiction for local requirements.