Is a 60 amp breaker correct for a 10 kw 220 heat strip?

1 answer

Answer

1259910

2026-03-02 03:00

+ Follow

10 kW at 220v will use 45.45 Amps. I'd recommend a 60A circuit, with a 60A breaker, but the heater or electric furnace should have "maximum fuse amps" rated on its nameplate. Above all, neverconnect wiring to a breaker that is rated higher than the maximum current capacity of the wire. In the case of 60A, use #6 AWG wire.