The stability and sensitivity test shall be performed for unit protection to prove
the stability for through fault and sensitivity for the internal faults. The principle
of the test is as followed.
The protected zone of unit protection is restricted by location of the CTs. For
stability test the primary current shall be injected through one set of two CTs
such a way one of current inwards and other outwards. At relay terminal no
operating current shall be observed for proper connection. Sensitivity test shall
be conducted with same set-up with either reversed CT polarity or injecting
primary current on only one CT of the set. At relay terminal, operating current
shall be observed for proper function.