What is the value of fail megger test result?

1 answer

Answer

1281764

2026-04-30 01:05

+ Follow

Engineers request that 5 meg ohm is the bottom limit. I use 1 meg as a bottom limit when megging conductors before they are energized. I have run motors as low as .5 meg, when the moisture is driven out by the heat of the motors operation the motors usually climbs up to about 2 meg ohms.