What is the no load current of a 2.2kW 3 phase 415V AC Motor?

1 answer

Answer

1152900

2026-04-27 17:45

+ Follow

Divide 2.2 kW by (an assumed, because you did not state it) power factor of 0.85 to get 2.6 kVA. Divide that by 3 to get 0.863 KVA per winding. Divide that by 415 volts to get 2.08 amperes per winding. If you are running star, then that is the phase current. If you are running delta, then multiply by the square root of 3 (1.732) to get 3.6 amperes per phase.