Why a 3 phase fault is more severe than other fault in transmission line?

1 answer

Answer

1159880

2026-06-01 10:20

+ Follow

It isn't necessarily (depending on your perspective). A three phase fault is a severe duty on generators, because all three phases are shorted. In solidly grounded systems a phase to ground fault could result in higher magnitude currents, which would be more difficult for a breaker to interrupt (so from the breaker's perspective, this would be more severe).