For single phase, KVA = (line to ground) * (phase current).
A 75kVA 480 to 208Y/120 volt transformer is a fairly common transformer. I assume this is the type of transformer you are referring to. 75k / 120 = 625 Amps.
As an FYI, the 208Y voltage is the line to line voltage, which is equal to (phase 1) - (phase 2), where the phases are separated by 120 degrees, thus (phase 1) * 1.732
For three phase, kVA = (line to line voltage) * (phase current) *(sqrt 3),
75k / 208 / 1.732 = 208 Amps.