Step 1: calculating knee point voltage Vkp
Vkp = {2 x Ift (Rct+Rw)}/ k
Vkp = required CT knee point voltage
Ift = max transformer through fault in ampere
Rct = CT secondary winding resistance in ohms
Rw = loop impedance of pilot wire between CT and the
K = CT transformation ratio
Step 2: calculate Transformer through fault Ift
Ift = (KVA x 1000)/(1.732 x V x Impedance)
KVA = transformer rating in kVA
V = transformer secondary voltage
Impedance = transformer impedance
Step 3: How to obtain Rct
To measure when CT is produce
Step 4: How to obtain Rw
This is the resistance of the pilot wire used to connect the 5th class X CT at the transformer star point to the relay
in the LV switchboard. Please obtain this data from the Electrical contractor or consultant. We provide a table to
serve as a general guide on cable resistance.
Example:
Transformer Capacity : 2500kVA
Transformer impedance : 6%
Voltage system : 22kV / 415V 3phase 4 wire
Current transformer ratio : 4000/5A
Current transformer type : Class X PR10
Current transformer Vkp : 185V
Current transformer Rct : 1.02½ (measured)
Pilot wire resistance Rw : 25 meters using
6.0mm sq cable
= 2 x 25 x 0.0032
= 0.16½
Ift = (kVA x 1000) / (1.732 x V x impedance)
= (2500 x 1000) / (1.732 x 415 x 0.06)
= 57,968 round up 58,000A
Vkp = {2 x Ift (Rct+Rw) } / k
= {2 x 58000 (1.02+0.16) } / 800
= 171.1½
Copyright © 2026 eLLeNow.com All Rights Reserved.