Answer for USA, Canada and countries running a 60 Hz supply service.
The NEC and CEC requires a distance of 3 ft. (1 meter) in front of a panel, a width of 30 inches or the width of the panel, whichever is greater, and a height of 6 1/2 feet or the height of the panel, whichever is greater, to be clear of obstructions. Any door or hinged cover must be able to be opened to a 90 degree angle. There needs to be enough room to work in the panel even when energized to do the work safely.
THIS AREA SHALL NOT BE USED FOR STORAGE !!!
<><><>
As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.
Before you do any work yourself,
on electrical circuits, equipment or appliances,
always use a test meter to ensure the circuit is, in fact, de-energized.
IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB
SAFELY AND COMPETENTLY
REFER THIS WORK TO QUALIFIED PROFESSIONALS.